Boiling Heat Transfer and Pressure Drop of Non-Azeotropic Mixtures Inside a Horizontal Grooved Tube

Bibliographic Information

Other Title
  • 非共沸混合冷媒の水平溝付管内沸騰熱伝達と圧力損失

Search this article

Abstract

The evaporation of HCFC141b, HFC152a and HFC23, and non-azeotropic refrigerant mixture used at the very low temperature refrigeration system is experimentally studied in a horizontal spirally grooved tube with corrugation.<br>The experiments were conducted at 0.03 to 0.47MPa of boiling pressure, 100 kg/(m2s) of mass flux, 1 to 15 kW/ m2 of heat flux, -26 to 21 °C of refrigerant temperature and 11.4 mm of average inner diameter.<br>It is concluded that boiling heat transfer coefficients of single-refrigerant are higher than these of non-azeotropic refrigerant mixture. And dimensionless correlation of the heat transfer coefficirnts, i.e. Lockhart-Martinelli parameters agreed with equation (10) within the limit of ±40 percent. Pressure drops of these refrigerant mixture depend on its liquid density and flow pattern.

Journal

References(14)*help

See more

Details 詳細情報について

  • CRID
    1390001204666307712
  • NII Article ID
    10002713144
  • NII Book ID
    AN10035654
  • DOI
    10.11322/tjsrae.12.53
  • ISSN
    2185789X
    13444905
  • Text Lang
    ja
  • Data Source
    • JaLC
    • CiNii Articles
  • Abstract License Flag
    Disallowed

Report a problem

Back to top