過冷却水を利用した氷蓄熱システム -第2報 : 蓄氷および解氷特性- An Ice Storage System Using Supercooled Water 2st Report : Ice Storage and Melting Characteristics

この論文にアクセスする

この論文をさがす

著者

抄録

The storage and melting characteristics of slurry-ice mixtures in several tanks were investigated exprimentally. For ice storage processes, three different kinds ofice-feeding methods were tested in connection with the fluidizable water-ice two-phase mixture produced in the system. It was confirmed that the achievable bulk IPF in any tank and using any of these methods was 30-40% under stable operational conditions. For ice melting processes, two different kinds of methods were considered and tested. Both were advantageous in that almost all ice stored in a tank could be consumed, thereby maintaining high system performance. By a modeling analysis of ice melting processes in the tank, it was possible to predict accurately the time history of tank outlet water temperatures.

収録刊行物

  • 日本冷凍協会論文集  

    日本冷凍協会論文集 12(3), 263-273, 1995-11-01 

    Japan Society of Refrigerating and Air Conditioning Engineers

参考文献:  10件

参考文献を見るにはログインが必要です。ユーザIDをお持ちでない方は新規登録してください。

被引用文献:  3件

被引用文献を見るにはログインが必要です。ユーザIDをお持ちでない方は新規登録してください。

各種コード

  • NII論文ID(NAID)
    10002713497
  • NII書誌ID(NCID)
    AN10035654
  • 本文言語コード
    JPN
  • 資料種別
    ART
  • ISSN
    09100040
  • データ提供元
    CJP書誌  CJP引用  J-STAGE 
ページトップへ