過冷却水を利用した氷蓄熱システム

書誌事項

タイトル別名
  • An Ice Storage System using Supercooled Water
  • ―第2報:蓄氷および解氷特性―
  • 2st Report : Ice Storage and Melting Characteristics

この論文をさがす

抄録

The storage and melting characteristics of slurry-ice mixtures in several tanks were investigated exprimentally. For ice storage processes, three different kinds ofice-feeding methods were tested in connection with the fluidizable water-ice two-phase mixture produced in the system. It was confirmed that the achievable bulk IPF in any tank and using any of these methods was 30-40% under stable operational conditions. For ice melting processes, two different kinds of methods were considered and tested. Both were advantageous in that almost all ice stored in a tank could be consumed, thereby maintaining high system performance. By a modeling analysis of ice melting processes in the tank, it was possible to predict accurately the time history of tank outlet water temperatures.