過冷却水を利用した氷蓄熱システム -第3報 : 経済的要因分析- An Ice Storage System Using Supercooled Water 3st Report : Economic Analysis of System Design Factors

この論文にアクセスする

この論文をさがす

著者

抄録

The economic aspects of an ice storage system employing supercooled water were compared with those of a chilled water system. In this analysis, the characteristics of the thermal storage tank and the system-COP were selected as technological factors, that have particular relevance to the economic issues at introduction of tharmal storage systems. <br>The following results were obtained : <br>(1) The cooling rate of the ice storage system was comparable with the rate of a chilled water storage system.<br>(2) The cooling rate of the ice storage system was not hardly influenced by the cost of thermal storage tank. <br>(3) In the hybrid thermal storage system, the ice storage system could surely satisfy the requirement for large peak shift.