2熱源駆動一重二重効用併用型吸収式冷凍機の特性 第1報 : 水蒸気と温水により駆動する吸収式冷凍機の特性に関する実験的検討 Characteristics of Single/Double-Effect Combination Absorption Refrigerator 1st Report : The Experimental Investigation about the Characteristics of Absorption Refrigerator Driven by Steam and Hot Water

この論文にアクセスする

この論文をさがす

著者

抄録

In recent years, co-generation system with fuel cell occupies the attention of the world from a standpoint of the environmental protection and the effective utilization of the energy. Since the waste heat of phosphoric acid fuel cell is recovered in two forms of steam (0.6 [MPa]) and hot water (65∼90 [°C]), this type of absorption refrigerator is driven by two heat sources.<br>In this paper, we inquire the result of the experiment intented for this absorption refrigerator the standard cooling capacity of which is 35[kW]. It is recognized that there is a mutual intervention when the supply condition of steam pressure is changed. Also the effects of hot water temperature, cooling water temperature and chilled water temperature for the performance of this absorption refrigerator is clarified. As a result, the effectiveness of using steam and hot water simultaneously in year-round operation is shown. Furthermore, it is clarified that the utilization of the low boiling temperature medium as the heat transfer medium for air-conditioner is effective.

収録刊行物

  • 日本冷凍協会論文集  

    日本冷凍協会論文集 13(2), 187-197, 1996-07-31 

    Japan Society of Refrigerating and Air Conditioning Engineers

参考文献:  10件

参考文献を見るにはログインが必要です。ユーザIDをお持ちでない方は新規登録してください。

被引用文献:  2件

被引用文献を見るにはログインが必要です。ユーザIDをお持ちでない方は新規登録してください。

各種コード

  • NII論文ID(NAID)
    10002713679
  • NII書誌ID(NCID)
    AN10035654
  • 本文言語コード
    JPN
  • 資料種別
    ART
  • ISSN
    09100040
  • NDL 記事登録ID
    4020805
  • NDL 雑誌分類
    ZN14(科学技術--機械工学・工業--熱機関)
  • NDL 請求記号
    Z16-1394
  • データ提供元
    CJP書誌  CJP引用  NDL  J-STAGE 
ページトップへ