Estimation Model of Leader Breakdown Field Strength in SF<sub>6</sub> Inhomogeneous Gaps Under Positive Lightning Impulse Voltage

Bibliographic Information

Other Title
  • 正極性雷インパルスに対するSF<sub>6</sub>不平等ギャップの破壊電界評価モデル
  • 正極性雷インパルスに対するSF6不平等ギャップの破壊電界評価モデル
  • セイキョクセイ カミナリインパルス ニ タイスル SF6 フビョウドウ ギャッ

Search this article

Abstract

This paper deals with leader breakdown characteristics of SF6 inhomogeneous gaps under positive lightning impulse voltages. The high voltage electrode is a thin aluminum sheet whose thickness is 100μm, the grounded electrode is a plane electrode, and gap length is 50mm. To control the electric field at edges of the sheet electrode, we used the electric shields that are four types. <br>It is found out that breakdown voltages can be estimated by a supposition of space charge which acts like the electrodes around the edges of the sheet electrode. We named this space charge "Imaginary Electrode", When the electric field of Imaginary Electrode surface reaches the critical field, a leader breakdown occurs. With the present experimental electrodes, electric shields don't affect the radius of Imaginary Electrode, but gas pressure affects the radius of Imaginary Electrode, which is 0.25mm at 0.5MPa, 0.5mm at 0.3MPa, and 3.0mm at 0.1MPa. This gas pressure dependency of the radius of Imaginary Electrode is influenced by the structure of inhomogeneous electrodes.

Journal

Citations (2)*help

See more

References(6)*help

See more

Details 詳細情報について

Report a problem