吸着式除湿冷房用水噴霧式熱交換器による空気の冷却性能の実験的研究

書誌事項

タイトル別名
  • Experimental Study of Air Cooling by Water Spray Heat Exchanger for Adsorptive Desiccant Cooling System.
  • キュウチャクシキ ジョシツ レイボウ ヨウミズ フンムシキ ネツ コウカンキ

この論文をさがす

抄録

A hot air stream was successfully cooled across the heat transfer surface of a cross-flow finned plate heat exchanger with honeycomb structure of aluminum while fine water droplets accompanied in excess over saturation were evaporated in a cold air stream. Hot stream temperature efficiency is improved over that without sprayed droplets and attained up to 60% in a typical example, even at high ratio of hot/cold air flow rate of 4 and a small fraction of water droplets, as small as 0.3% wt. The effect of flow rate ratio and amount of accompanied droplets on heat transfer performance is investigated to propose a scheme of so-called self cooling in which a cold air stream was prepared by spraying water droplets to a part of process air. Thus cooling under constant humidity reduces enthalpy in contrast to the conventional direct contact evaporative cooler at constant enthalpy. A high value of COP is expected in an adsorptive desiccant cooling system equiped with the present sprayed heat exchanger.