書誌事項
- タイトル別名
-
- High Precision Determination Methods of Time to Peak of Switching Impulse Voltage
- カイヘイ インパルス デンアツ ノ コウ セイド ハトウチョウ サンシュツ
この論文をさがす
抄録
In IEC publication 60060-1, “high-voltage test techniques”, the time to peak Tp of the switching impulse voltage is defined as “the time interval between the actual origin and the instant when the voltage has reached its peak value”. In this case, it is very difficult to determine precisely the time to peak due to the flatness of the switching impulse around the peak. The situation becomes even more so when digitally recorded switching impulse data include noise around the peak.<br> Therefore, IEC 61083-2, “Digital recorders for measurements in high voltage impulse tests” introduced, as an appendix, an approximation formula which determines the value of Tp from the interval time between the instants when the switching impulse reaches 30% and 90% of the peak value in its front.<br> Authors checked the formula and propose more precise approximation formula and a graphical method. The details of the newly proposed methods are discussed in this paper.
収録刊行物
-
- 電気学会論文誌B(電力・エネルギー部門誌)
-
電気学会論文誌B(電力・エネルギー部門誌) 118 (5), 548-554, 1998
一般社団法人 電気学会