Abstract
Partial Discharge (PD) within voids in solid insulating system is a symptom and/or a direct cause of a deterioration of stator windings of a turbine generator. The bandwidth of the electromagnetic waves emitted from PD is very broad and ranges to GHz. We developed a new system based on “Spatial Phase Difference Method” for detecting microwave (GHz) emitted from PD. In this paper we applied this system to two off-line turbine generators in the overhaul and an on-line turbine generator which has two built-in antennas. On-line PD detection of the turbine generator is very useful for recognizing abnormal and/or deteriorated stator winding insulation without a machine outage. It was found that the detection system was able to detect microwave emitted from PD in operating turbine generator.
Journal
-
- IEEJ Transactions on Power and Energy
-
IEEJ Transactions on Power and Energy 118 (11), 1243-1248, 1998
The Institute of Electrical Engineers of Japan
- Tweet
Keywords
Details 詳細情報について
-
- CRID
- 1390001204604874368
-
- NII Article ID
- 130006841331
- 10008217045
- 10002877162
-
- NII Book ID
- AN10136334
-
- ISSN
- 13488147
- 03854213
-
- NDL BIB ID
- 4588400
-
- Data Source
-
- JaLC
- NDL
- Crossref
- CiNii Articles
-
- Abstract License Flag
- Disallowed