Dielectric Characteristics of Insulation Models for Oil filled Transformer under Very Fast Transient voltages
-
- Inoue Tamotsu
- TOSHIBA Corporation
-
- Teranishi Tsuneharu
- TOSHIBA Corporation
-
- Taniguchi Yasuhiko
- TOSHIBA Corporation
-
- Ebisawa Yoshihito
- TOSHIBA Corporation
-
- Ikeda Masami
- TOSHIBA Corporation
Bibliographic Information
- Other Title
-
- 油入変圧器絶縁モデルの急峻波電圧領域の絶縁特性
- アブライリ ヘンアツキ ゼツエン モデル ノ キュウシュンハ デンアツ リョウ
Search this article
Abstract
This paper deals with the partial discharge inception voltage(PDIV) and breakdown voltage(BDV) characteristics of turn-to-turn insulation models for oil filled transformers under steep front short duration pulse voltages, of which wave forms are 35/70ns and 50/370ns. It was found that BDV's under nano-second pulse were 1.2_??_1.4 times higher than those under standard impulse voltage.