Control and Protection Scheme of HVDC System with Self-commutated converter in System Fault Conditions

Bibliographic Information

Other Title
  • 自励式直流送電システムにおける系統事故時の制御保護方式
  • ジレイシキ チョクリュウ ソウデン システム ニ オケル ケイトウ ジコジ ノ

Search this article

Abstract

For extending self-commutated converter application to future trunk power system, it is important to develop stable operation scheme as well as to realize substantial cost reduction through coordinated system and control design. Suppression controls of converter overcurrent and dc overvoltage in various system fault conditions are essentially needed to ensure stable operation and cost reduction of HVDC system with voltage source type self-commutated converter. Converter control and protection schemes which include such suppression controls have been developed employing CRIEPI's AC•DC Power System Simulator test and EMTP analysis.<br> This paper first discusses the cause of converter overcurrent at ac system fault considering the effect of PWM pulse number and converter control speed. Continued operation has been achieved by adding a new overcurrent suppression scheme into the converter control. In a condition of dc line grounding fault, the selection of grounding circuit constant and the adoption of high speed converter control practically ensure the reduction of dc overvoltage while suppressing converter overcurrent. Converter block and restart sequence after de fault, which is coordinated with dc circuit breaker operation, enables stable recovery of HVDC transmission as fast as the usual line-commutated HVDC system.

Journal

Citations (8)*help

See more

References(10)*help

See more

Details 詳細情報について