スローバンク故障時に流入する直流大電流の油中遮断保護方式 Protective Systems for Breaking of DC Large Current in Oil on Local Failures of Slow-Capacitor Bank

この論文にアクセスする

この論文をさがす

著者

抄録

The accidental electric breakdown in arbitrary one of capacitors in a parallel connection of the large slow-capacitor bank may result in serious damages such as mechanical explosion and oil effusion or fire.<br>Because, breaking of the DC large current of follow in to a breakdown capacitor from normal capacitors is impossible. Therefore, many kinds of protective devices were made designed.<br>We do report how to get new knowledge about succeeding breaking of DC large current in oil by experiments.<br>Our view point is effect of surge absorption by parallel normal capacitors conected to the breaking device in accidental electric breakdown capacitor.<br>The result showed that breaking time is a value less than 2 milliseconds for a parallel connection bank more than 3 capacitors, each one is a SH-type capacitor (1200V in DC, 1200μF).

収録刊行物

  • 電気学会論文誌. D, 産業応用部門誌 = The transactions of the Institute of Electrical Engineers of Japan. D, A publication of Industry Applications Society  

    電気学会論文誌. D, 産業応用部門誌 = The transactions of the Institute of Electrical Engineers of Japan. D, A publication of Industry Applications Society 119(8), 1037-1043, 1999-08 

    The Institute of Electrical Engineers of Japan

参考文献:  10件

参考文献を見るにはログインが必要です。ユーザIDをお持ちでない方は新規登録してください。

各種コード

  • NII論文ID(NAID)
    10004296997
  • NII書誌ID(NCID)
    AN10012320
  • 本文言語コード
    JPN
  • 資料種別
    ART
  • ISSN
    09136339
  • NDL 記事登録ID
    4816613
  • NDL 雑誌分類
    ZN31(科学技術--電気工学・電気機械工業)
  • NDL 請求記号
    Z16-1608
  • データ提供元
    CJP書誌  NDL  J-STAGE 