500kV送電線を対象とした雷観測結果(その1)

書誌事項

タイトル別名
  • Observation of Lightning at 500kV Transmission Lines (Part 1)
  • 500kV ソウデンセン オ タイショウ ト シタ カミナリ カンソク ケッカ

この論文をさがす

抄録

We observed winter lightning on 500kV transmission lines from 1984 to 1993. The observation was lightning course by camera and lightning current at the lower part of transmission tower on 31 towers, in 12.7 kilo-meter transmission lines. And we also observed lightning on isolated tower in nuclear power station.<br> Through the ten-years lightning observations, we have confirmed lightning protection design on transmission line. The distribution of lightning incidence angle (θ) was m=2 (cosm θ) for the 3 dimensional case, and m=3.5 for the 2 dimensional. We had no case of shield missing on 500kV transmission lines. The ratio of lightning current at the top of isolated tower to the lower part was about 11 to 1. And the lightning current waveform at the top of isolated tower was similar to the one at the lower part.

収録刊行物

被引用文献 (5)*注記

もっと見る

参考文献 (11)*注記

もっと見る

キーワード

詳細情報 詳細情報について

問題の指摘

ページトップへ