ロゴスキーコイルによる零相電流検出の特性向上に関する検討 Improvement of Characteristics of Zero-Phase-Sequence Current Detector by Using Rogowski Coils

この論文にアクセスする

この論文をさがす

著者

抄録

This paper describes the improving method of Rogowski coil for the measurements of zero-phase-sequence current. For the measurements of zero-phase-sequence current, the error made by the influence of external magnetic field and residual current is explained and verified in this paper. In new winding method, two wires are used to wind with different winding directions at the start. This winding method makes the crossing point at the opposite side of the coil, and two wires should be crossed up and down alternately to form the same size of cross section of the coil. The coil is divided to several pieces of small coils. The outputs of these coils are connected in parallel. It is observed that the influence of external magnetic field and residual current is improved tremendously by this new improvement.

収録刊行物

  • 電気学会論文誌. B, 電力・エネルギー部門誌 = The transactions of the Institute of Electrical Engineers of Japan. B, A publication of Power and Energy Society  

    電気学会論文誌. B, 電力・エネルギー部門誌 = The transactions of the Institute of Electrical Engineers of Japan. B, A publication of Power and Energy Society 126(11), 1112-1120, 2006-11-01 

    The Institute of Electrical Engineers of Japan

参考文献:  6件