Characteristics of Dry-Band Arcing on Fiber Ropes for Wiring Works Near Transmission Lines
-
- Ikeda Yasuaki
- Tokyo Electric power Co., Ltd.
-
- Umezawa Naoto
- Tokyo Electric power Co., Ltd.
-
- Yamagata Yoshibumi
- Tokyo Electric power Co., Ltd.
Bibliographic Information
- Other Title
-
- 送電線近接作業における繊維ロープのドライバンドアーク放電特性
- ソウデンセン キンセツ サギョウ ニ オケル センイ ロープ ノ ドライバンドアーク ホウデン トクセイ
Search this article
Abstract
Troubles related to damage of fiber ropes for wiring have sometimes occurred in case of wiring works close to energized transmission lines. Therefore, in order to establish a guideline on the treatment of fiber ropes for wiring works near transmission lines, authors implemented a damage test on the condition of high electric field, then examined the damage characteristics and mechanism. In this paper, mechanism of the dry-band arcing occurring as a result of concentration of voltage across the dry-bands, which are generated by the joule heat caused by the current induced to the wet fiber rope, is shown. In addition, the occurrence condition of the dry-band arcing acquired by the applied voltage test is described.
Journal
-
- IEEJ Transactions on Power and Energy
-
IEEJ Transactions on Power and Energy 126 (11), 1149-1156, 2006
The Institute of Electrical Engineers of Japan
- Tweet
Details
-
- CRID
- 1390001204602051456
-
- NII Article ID
- 10018318111
-
- NII Book ID
- AN10136334
-
- ISSN
- 13488147
- 03854213
-
- NDL BIB ID
- 8560758
-
- Text Lang
- ja
-
- Data Source
-
- JaLC
- NDL
- Crossref
- CiNii Articles
-
- Abstract License Flag
- Disallowed