Advanced Analysis of Grid-connected PV System's Performance and Effect of Battery

Bibliographic Information

Other Title
  • 系統連系型太陽光発電システム運転特性の高度解析と蓄電池導入効果の検証
  • ケイトウレンケイガタ タイヨウコウ ハツデン システム ウンテン トクセイ ノ コウド カイセキ ト チクデンチ ドウニュウ コウカ ノ ケンショウ

Search this article

Abstract

An advanced analysis method for grid connected PV systems is developed in this research. To investigate the issues which may happen in the clustered PV systems, “Demonstrative research on clustered PV systems" is being conducted from December, 2002, in Oota, Japan. More than 500 residential PV systems will be installed in the demonstrative research area, battery integrated PV systems are developed to avoid the restriction of output power due to the raising of grid voltage. Annual performance of commercial PV systems without battery is analyzed and resulted in around 80% of performance ratio on the average. Over voltage of power distribution line and snow are two major factors of very low performance ratio on daily basis. Effects of batteries are also analyzed, the results indicate that there will be some improvement for the energy loss due to the grid voltage but PCS's efficiency will be around 8% worse than that of the commercial PV systems. It is also found that the non-optimized operation of battery sometimes results in the fully-charged situation during the noontime and maximum reverse power flow may not be minimized in this situation.

Journal

Citations (6)*help

See more

References(11)*help

See more

Details 詳細情報について

Report a problem

Back to top