最大2次アーク電流最小化を目的とした2回線UHV送電線用線路直付リアクトル最適設計手法 Simple Optimizing Method of Shunt Reactor Connected to Double Circuit UHV Transmission Line for Minimizing Maximum Secondary Arc Current

この論文にアクセスする

この論文をさがす

著者

抄録

On UHV transmission line, it is known that the secondary arc extinction time after clearing fault arc will be long and there is a possibility of auto-reclosing failure. Connecting shunt reactors with a neutral reactor to the transmission line is one way to reduce the secondary arc extinction time. Double circuit transmission line requires consideration of inter-circuit capacitance as well as inter-phase capacitance, which causes difficulty in configuring optimal shunt reactor. This paper proposes a simple method optimizing the shunt reactors connected to the double circuit transmission line.

収録刊行物

  • 電気学会論文誌. B, 電力・エネルギー部門誌 = The transactions of the Institute of Electrical Engineers of Japan. B, A publication of Power and Energy Society  

    電気学会論文誌. B, 電力・エネルギー部門誌 = The transactions of the Institute of Electrical Engineers of Japan. B, A publication of Power and Energy Society 127(1), 335-336, 2007-01-01 

    The Institute of Electrical Engineers of Japan

参考文献:  4件

参考文献を見るにはログインが必要です。ユーザIDをお持ちでない方は新規登録してください。