分散型電源連系配電ネットワークの標準解析モデルの構築とネットワーク構成候補の多面的評価手法の開発 Establishment of a Standard Analytical Model of Distribution Network with Distributed Generators and Development of Multi Evaluation Method for Network Configuration Candidates

この論文にアクセスする

この論文をさがす

著者

    • 林 泰弘 HAYASHI Yasuhiro
    • 福井大学 大学院工学研究科 電気・電子工学専攻 Graduate School of Electrical and Electronics Engineering, University of Fukui
    • 川崎 章司 KAWASAKI Shoji
    • 福井大学 大学院工学研究科 電気・電子工学専攻 Graduate School of Electrical and Electronics Engineering, University of Fukui
    • 松木 純也 [他] MATSUKI Junya
    • 福井大学 大学院工学研究科 電気・電子工学専攻 Graduate School of Electrical and Electronics Engineering, University of Fukui
    • 松田 浩明 MATSUDA Hiroaki
    • 福井大学 大学院工学研究科 電気・電子工学専攻 Graduate School of Electrical and Electronics Engineering, University of Fukui
    • 酒井 重和 SAKAI Shigekazu
    • 福井大学 大学院工学研究科 電気・電子工学専攻 Graduate School of Electrical and Electronics Engineering, University of Fukui
    • 宮崎 輝 MIYAZAKI Teru
    • 東京電力(株)技術開発研究所 高電圧・絶縁技術グループ High Voltage & Insulation Group, R&D Center, Engineering R&D Division, Tokyo Electric Power Company
    • 小林 直樹 KOBAYASHI Naoki
    • 東京電力(株)電力流通本部 配電部 配電技術グループ Distribution Engineering Group, Distribution Department, Power Network Division, Tokyo Electric Power Company

抄録

Since a distribution network has many sectionalizing switches, there are huge radial network configuration candidates by states (opened or closed) of sectionalizing switches. Recently, the total number of distributed generation such as photovoltaic generation system and wind turbine generation system connected to the distribution network is drastically increased. The distribution network with the distributed generators must be operated keeping reliability of power supply and power quality. Therefore, the many configurations of the distribution network with the distributed generators must be evaluated multiply from various viewpoints such as distribution loss, total harmonic distortion, voltage imbalance and so on. In this paper, the authors propose a multi evaluation method to evaluate the distribution network configuration candidates satisfied with constraints of voltage and line current limit from three viewpoints ((1) distribution loss, (2) total harmonic distortion and (3) voltage imbalance). After establishing a standard analytical model of three sectionalized and three connected distribution network configuration with distributed generators based on the practical data, the multi evaluation for the established model is carried out by using the proposed method based on EMTP (Electro-Magnetic Transients Programs).

収録刊行物

  • 電気学会論文誌. B, 電力・エネルギー部門誌 = The transactions of the Institute of Electrical Engineers of Japan. B, A publication of Power and Energy Society  

    電気学会論文誌. B, 電力・エネルギー部門誌 = The transactions of the Institute of Electrical Engineers of Japan. B, A publication of Power and Energy Society 126(10), 1013-1022, 2006-10-01 

    The Institute of Electrical Engineers of Japan

参考文献:  18件

参考文献を見るにはログインが必要です。ユーザIDをお持ちでない方は新規登録してください。

被引用文献:  16件

被引用文献を見るにはログインが必要です。ユーザIDをお持ちでない方は新規登録してください。

各種コード

  • NII論文ID(NAID)
    10018780842
  • NII書誌ID(NCID)
    AN10136334
  • 本文言語コード
    JPN
  • 資料種別
    ART
  • ISSN
    03854213
  • NDL 記事登録ID
    8526392
  • NDL 雑誌分類
    ZN31(科学技術--電気工学・電気機械工業)
  • NDL 請求記号
    Z16-794
  • データ提供元
    CJP書誌  CJP引用  NDL  J-STAGE 
ページトップへ