住宅用コジェネが大量導入された配電系統電圧の統計的評価

書誌事項

タイトル別名
  • Statistical Evaluation of Voltage Variation of Power Distribution System with Clustered Home-Cogeneration Systems
  • ジュウタクヨウ コジェネ ガ タイリョウ ドウニュウサレタ ハイデン ケイトウ デンアツ ノ トウケイテキ ヒョウカ

この論文をさがす

抄録

This paper discusses the influence of mass installation of a home co-generation system (H-CGS) using a polymer electrolyte fuel cell (PEFC) on the voltage profile of power distribution system in residential area. The influence of H-CGS is compared with that of photovoltaic power generation systems (PV systems). The operation pattern of H-CGS is assumed based on the electricity and hot-water demand observed in 10 households for a year. The main results are as follows. With the clustered H-CGS, the voltage of each bus is higher by about 1-3% compared with the conventional system without any distributed generators. Because H-CGS tends to increase the output during the early evening, H-CGS contributes to recover the voltage drop during the early evening, resulting in smaller voltage variation of distribution system throughout a day. Because of small rated power output about 1kW, the influence on voltage profile by the clustered H-CGS is smaller than that by the clustered PV systems. The highest voltage during the day time is not so high as compared with the distribution system with the clustered PV systems, even if the reverse power flow from H-CGS is allowed.