Dynamic Behaviour of DFIG-Based Wind Turbines During Grid Faults
-
- Erlich Istvan
- University Duisburg-Essen
-
- Wrede Holger
- SEG GmbH & Co. KG
-
- Feltes Christian
- University Duisburg-Essen
この論文をさがす
抄録
According to grid codes issued by utilities, tripping of wind turbines following grid faults is not allowed. Besides, to provide voltage support to the grid mandatory reactive current supply is necessary. To enable wind turbines ride-through low voltage periods special protection measures have to be implemented. In this paper the behavior of DFIG based wind turbines during grid faults is discussed and elucidated using simulation results. It is shown that with properly designed crowbar and DC-link chopper even zero voltage ride-through is possible.
収録刊行物
-
- 電気学会論文誌D(産業応用部門誌)
-
電気学会論文誌D(産業応用部門誌) 128 (4), 396-401, 2008
一般社団法人 電気学会
- Tweet
詳細情報 詳細情報について
-
- CRID
- 1390282679634828672
-
- NII論文ID
- 10021133853
-
- NII書誌ID
- AN10012320
-
- BIBCODE
- 2008IJTIA.128..396E
-
- ISSN
- 13488163
- 09136339
-
- NDL書誌ID
- 9453596
-
- 本文言語コード
- en
-
- データソース種別
-
- JaLC
- NDL
- Crossref
- CiNii Articles
-
- 抄録ライセンスフラグ
- 使用不可