マルチエージェントによる分散型無効電力制御方式

書誌事項

タイトル別名
  • Multi-agent based Distributed Reactive Power Control Method
  • マルチエージェント ニ ヨル ブンサンガタ ムコウ デンリョク セイギョ ホウシキ

この論文をさがす

抄録

In order to maintain system voltage within the optimal range and prevent voltage instability phenomena before they occur, a variety of phase modifying equipment is installed in optimal locations throughout the power system network and a variety of methods of voltage reactive control are employed. In this paper, the voltage reactive control problem is considered as the two sub problems such as voltage control and reactive power control. The proposed multi-agent system intends to resolve the reactive power control sub problem. In this system, three types of agents are installed in substations in order to maintain the primary bus voltage within the operation limit by allocating the reactive power.<br>In order to verify the performance of the proposed method, it has been applied to the model network system. The simulation results show that the proposed method is a promising approach to keep the primary bus voltage within the operational limit by changing the reactive power allocation.

収録刊行物

参考文献 (19)*注記

もっと見る

詳細情報 詳細情報について

問題の指摘