耐熱絶縁紙の油中加熱劣化特性と劣化メカニズムの推定

書誌事項

タイトル別名
  • Aging Effects and Estimating Degradation Mechanisms of Thermally Upgraded Paper in Mineral Oil
  • タイネツ ゼツエンシ ノ ユチュウ カネツ レッカ トクセイ ト レッカ メカニズム ノ スイテイ

この論文をさがす

抄録

The life of a transformer is limited to the deterioration of its solid insulation. Winding conductors and other solid insulation materials in oil-immersed transformers have been insulated using cellulose products. For many years, manufacturers have met the needs of special applications by designing transformers using thermally upgraded materials to achieve lighter weight, higher power density and increased life. Recently, the effect of thermally upgraded insulation on diagnostic techniques such as gas-in oil analysis, and their indication of insulation degradation have been reviewed. This paper describes evaluations of the thermal degradation characteristics and decomposition reactions in mineral transformer oil of amine-impregnated thermally upgraded paper insulation. The thermal resistance of the thermally upgraded paper is evaluated by comparison with Kraft paper insulation. Further, aging degradation mechanisms of decompositional degradation of the thermally upgraded paper due to aging in mineral transformer oil are proposed.

収録刊行物

被引用文献 (2)*注記

もっと見る

参考文献 (20)*注記

もっと見る

詳細情報 詳細情報について

問題の指摘

ページトップへ