- タイトル別名
-
- The performance analysis of the absorption heat pump which can provide hot and cold heat
抄録
An absorption refrigerator is getting attentions as a waste heat recovery system in a cogeneration system. To improve the efficiency of the cogeneration system more, it is indispensable to improve even the efficiency of the absorption refrigerator driven by waste heat. But to drive the absorption refrigerator with waste heat, it is difficult to advance the cycle and improve the efficiency. From this reason, if the cold heat is only obtained, the efficiency can not be enhanced greatly. Therefore this research suggests the absorption heat pump which can supply the cold and the hot heat which has been conventionally rejected as the cooling heat in the absorber and condenser, and analyzes the performance of this system by the simulation. As a result, In mode 3, COP_T is the highest in three modes, and its value is 2.52 for the working fluids H_2O-LiBr+LiI+LiCl+LiNO_3 when the cold heat temperature is 5℃ and the hot heat is 50℃.
収録刊行物
-
- 環境工学総合シンポジウム講演論文集
-
環境工学総合シンポジウム講演論文集 2001.11 (0), 540-543, 2001
一般社団法人 日本機械学会