軸流型吹き出し口を用いた床吹き出し空調システムの室内温度分布特性 : 床吹き出し空調システムに関する研究 第1報  [in Japanese] ROOM AIR TEMPERATURE PROFILE OF UNDER-FLOOR AIR-CONDITIONING SYSTEM USING NOZZLE-TYPE OUTLET : Studies on under-floor air-conditioning system Part 1  [in Japanese]

Abstract

Space air temperature profile when cooled air was discharged from floor-mounted outlet was quantified through a number of experiments in a full-scale test chamber. Nozzle-type outlet was discussed as the first trial in the present paper. Space air temperature distribution was measured under steady-state in detail. The vertical temperature gradient of the room could be related to the throw of the cold air jet. Thus, uniform temperature distribution was formed in the region of approximately a half height of the throw. A simplified calculation model of the vertical temperature profile was also developed. It was suggested that, room space was divided into the completely mixing region and the piston flow region. The depth of the former zone was identified based on experimental results.

Journal

Journal of architecture, planning and environmental engineering. Transactions of AIJ   [List of Volumes]

Journal of architecture, planning and environmental engineering. Transactions of AIJ (452), 27-35, 1993-10-30  [Table of Contents]

Architectural Institute of Japan

References:  13

You must have a user ID to see the references.If you already have a user ID, please click "Login" to access the info.New users can click "Sign Up" to register for an user ID.

Cited by:  8

You must have a user ID to see the cited references.If you already have a user ID, please click "Login" to access the info.New users can click "Sign Up" to register for an user ID.

Preview

Preview

Codes

  • NII Article ID (NAID) :
    110004083152
  • NII NACSIS-CAT ID (NCID) :
    AN10040144
  • Text Lang :
    JPN
  • Article Type :
    Other
  • ISSN :
    09108017
  • NDL Article ID :
    3849364
  • NDL Source Classification :
    建築設備
  • NDL Source Classification :
    ZN1(科学技術--建設工学・建設業)
  • NDL Call No. :
    Z16-107
  • Databases :
    CJP  CJPref  NDL  NII-ELS