- MEASUREMENT OF CONVECTIVE HEAT TRANSFER COEFFICIENTS WITH USING AN EXPERIMENTAL AND COMPUTATIONAL THERMAL MANIKIN IN INDOOR ENVIRONMENTS
- ジッケン オヨビ スウチ サーマルマネキン オ モチイタ シツナイ カンキョウ ニ オケル ジンタイ カク ブイ ノ タイリュウ ネツ デンタツリツ ノ ソクテイ
この論文をさがす
抄録
The purpose of this study is to make a database of the local convective heat transfer coefficients (h_c)for each part of a human body in indoor environments. Values of the local h_c for a naked human body are determined based on both the results of experiments on a thermal manikin and analyses of the radiative heat transfer rate. The results are followed. (1) At the extreme parts of the human body, h_c is about 1.5W/m^2K higher than the average value for the whole body, and for the trunk parts are about 1.0W/m^2K lower than the average values in the state of standing and sedentary. (2) The value for the local h_c decreases as the human body approaches the furniture.