空調機と冷却塔の冗長性に関する検討 : 水冷パッケージ空調システムの信頼性評価に基づく冷却塔設計手法の研究 その2 STUDY ON REDUNDANT CONFIGURATIONS OF AIR-CONDITIONER AND COOLING TOWER : Design of water-cooled packaged air-conditioning systems based on reliability assessment Part 2

抄録

Water-cooled packaged air conditioner systems are gaining renewed recognition from the perspective of preventing the urban heat island phenomenon. Up to now, however, there have been no reliable methods for optimizing equipment capacity. For this reason, in telecommunications buildings, which demand high levels of reliability, there are cases of excessively redundant configurations, which not only result in reduced space efficiency, but also invite reduced operating efficiency due to partial load operations. In a previous report, we constructed a model for evaluating water-cooled packaged air conditioner systems, and demonstrated that it was possible to study equipment configurations based on these reliability evaluations. In this report, using this reliability evaluation model, we showed the equipment configurations required for each level of reliability. Furthermore, we proposed a design process using the reliability evaluation methods in this research, taking into account reduced capacity of the cooling tower resulting from the passage of time.

収録刊行物

日本建築学会環境系論文集   [巻号一覧]

日本建築学会環境系論文集 73(623), 53-60, 2008-01-30  [この号の目次]

社団法人日本建築学会

参考文献:  8件

参考文献を見るにはログインが必要です。ユーザIDをお持ちでない方は新規登録してください。

プレビュー

プレビュー

各種コード

  • NII論文ID(NAID) :
    110006547062
  • NII書誌ID(NCID) :
    AA11830377
  • 本文言語コード :
    JPN
  • 資料種別 :
    ART
  • ISSN :
    13480685
  • NDL 記事登録ID :
    9358864
  • NDL 雑誌分類 :
    ZN1(科学技術--建設工学・建設業)
  • NDL 請求記号 :
    Z74-D484
  • 収録DB :
    CJP書誌  NDL  NII-ELS