密閉式冷却塔によるフリークーリングの実験と計算方法に関する研究  [in Japanese] STUDY ON THE EXPERIMENT AND CALCULATION METHOD OF FREE COOLING SYSTEM WITH EVAPORATIVE COOLING TOWER  [in Japanese]

Abstract

Free cooling system is an energy saving system without chiller operation when the ambient temperature is relatively low and building needs the chilled water for cooling. The prediction method for free cooling performance is described in this paper with the theoretical formulae. The water temperature and the quantity of flow were measured in summer and winter in order to derive the parameters of the evaporative cooling tower. The predicted inlet and outlet water temperatures were agreed well with the measurement and it also shows the free cooling system with evaporative cooling tower may be available in Japan.

Journal

Journal of environmental engineering   [List of Volumes]

Journal of environmental engineering 73(625), 343-347, 2008-03-30  [Table of Contents]

Architectural Institute of Japan

References:  12

You must have a user ID to see the references.If you already have a user ID, please click "Login" to access the info.New users can click "Sign Up" to register for an user ID.