抄録
This paper presents an influence of latent heat load by changing relative humidity of air flow on distribution of super-heated gas region in an evaporator and an effect of refrigerant flow path pattern. To estimate the influence, we applied thermal network method that can take refrigerant quality distribution in the heat exchanger into account. If super-heated gas region spreads to upper wind row, humid air goes through the heat exchanger without drying, which means "air flow bypass". To suppress this phenomenon and simultaneously obtain the best performance, we chose optimum path pattern on the basis of this method. As a result the prediction shows that performance of the evaporator is recovered by 5% for a simple 2 rows and 2 paths heat exchanger when 40% of unbalance of air flow rate occurs.