A Study of the Regional Heat Discharge from Air Conditioning Systems and Related Devices Based on the Composition Ratio of Cooling Heat Source Devices

Bibliographic Information

Other Title
  • 冷熱源機器の導入割合を考慮した空調システムおよび関連機器の地域排熱量に関する研究
  • レイネツゲン キキ ノ ドウニュウ ワリアイ オ コウリョ シタ クウチョウ システム オヨビ カンレン キキ ノ チイキ ハイネツリョウ ニ カンスル ケンキュウ

Search this article

Abstract

This study aimed to understand regional heat discharge by means of thermal system analysis that considered the ratio of cooling heat source devices derived from a completed database of building equipment. The results showed a clear relationship between floor space and the ratio of latent heat to total heat released from air conditioning systems and related devices. This may have been due to the effect of cooling towers, which are mainly used in large buildings. The total amount of sensible heat released from air conditioning systems and related devices in the 23 wards of Tokyo was estimated using the GIS database of floor spaces. The results showed that summertime sensible heat in the 23 wards of Tokyo reached 13-14GW in the daytime, and 180GW・h per day. In addition, latent heat that was released from air conditioning systems and related devices in the 23 wards of Tokyo accounted for 25-28% of total daytime heat in the summer.

Journal

Citations (6)*help

See more

References(15)*help

See more

Details 詳細情報について

Report a problem

Back to top