民生業務用熱源システムにおける高効率ターボ冷凍機の使用法に関する研究 : 第2報-都市未利用熱源を冷却源とする熱源システムの省エネルギー性評価 Study about Operating Method of Latest Variable-Speed Centrifugal Chillers in Heat Source System for Business Use : Part2-Energy Consumption Evaluation of Heat Source System by Using Urban Unutilized Heat Source

抄録

最新のインバータターボ冷凍機では,回転数制御により部分負荷時の機械損失が大幅に低減され,成績係数は熱力学特性に大きく依存するため広い冷却水温度域に高い成績係数で追従することができる.本研究では民生業務用途に対し,最新インバータ機で冷却源を未利用熱源とした場合のエネルギー消費量を算定し,従来機と冷却塔を組み合わせた方式と比較することで,インバータ機の特性が未利用熱源の利用によるエネルギー消費量削減効果を従来機よりも大きく促進させることを明らかとした.

The variable-speed chiller has variable speed control and capacity control function of a compressor to minimize the mechanical loss in all operating ranges. Thus, the variable-speed chiller has a high COP feature in accordance with the thermodynamic property. The COP characteristic of the variable-speed chiller is different with that of the fixed-speed chiller. So, it has been considered that the conventional operating method is not appropriate to design and operate the heat source system with variable-speed chiller for business use. There also have been few reports about the heat source system with the variable-speed chiller, which uses the urban unutilized heat source. This report describes the validity and energy reduction effect of the variable-speed chiller by comparison of the energy consumption, which is calculated by numeric simulation, in case of urban unutilized heat source method (groundwater, swage water, river water, sea water) and general cooling tower method as cooling heat source in a heat source system with the latest fixed-speed chiller and a heat source system with the latest variable-speed chiller. The urban unutilized heat source method with the variable-speed chiller is more effect to reduce energy consumption than the cooling tower method with the fixed-speed chiller. Especially, effect of groundwater use is remarkable and the energy consumption is reduced by 50%. Even when energy reduction is not expected by the urban unutilized heat source method with the conventional chiller, the urban unutilized heat source method with the variable-speed chiller shows the reduction of energy consumption. These noteworthy results indicate that the variable-speed chiller is more effective in using urban unutilized heat source than the fixed-speed chiller due to the extremely low mechanical loss and the high COP characteristic in the small temperature difference between the evaporating temperature (the chilled water leaving temperature) and the condensing temperature (the cooling water entering temperature). In addition, by comparison of year-round energy consumption, the urban unutilized heat source usage is effective in summer and middle season, especially high reduction effect by groundwater, and cooling tower usage is effective in winter season by low wet-valve temperature and proper cooling tower control. In other words, when there is the cooling load throughout the year, it is suggested to use the urban unutilized heat source system in summer and middle season and cooling tower system in winter season. Consequently, the combination of the latest variable-speed chiller and the urban unutilized heat source is equivalent or more effective than the combination of the latest inverter chiller and the cooling tower regardless type of the urban unutilized heat source.

収録刊行物

空気調和・衛生工学会論文集   [巻号一覧]

空気調和・衛生工学会論文集 (144), 43-51, 2009-03-05  [この号の目次]

社団法人空気調和・衛生工学会

参考文献:  18件

参考文献を見るにはログインが必要です。ユーザIDをお持ちでない方は新規登録してください。

プレビュー

プレビュー

各種コード

  • NII論文ID(NAID) :
    110007996782
  • NII書誌ID(NCID) :
    AN00065706
  • 本文言語コード :
    JPN
  • 資料種別 :
    ART
  • ISSN :
    0385275X
  • NDL 記事登録ID :
    10193662
  • NDL 雑誌分類 :
    ZN5(科学技術--建設工学・建設業--都市工学・衛生工学)
  • NDL 請求記号 :
    Z16-955
  • 収録DB :
    CJP書誌  NDL  NII-ELS