D-52 土壌熱源ヒートポンプシステム設計支援ツールの開発とその応用 : その2 ボアホール内熱抵抗の算出とシステム性能への影響の考察
書誌事項
- タイトル別名
-
- D-52 Development of Design the Ground Source Heat Pump System and its Application : Part2 Calculation the Borehole Thermal Resistance and Consideration of the System Performance Borehole Thermal Resistance Influences
抄録
Authors calculated the borehole thermal resistance by boundary element method. Calculated the borehole thermal resistance is 0.127m^2K/W for a single U-tube heat exchanger and 0.086m^2K/W for a double U-tube heat exchanger when λ_g=1.8W/m/K, d_<Utube>=32mm, d_<bo>=120mm, d_<iUtube>=52mm as calculation conditions were given. When it makes the distance between supply pipe and return pipe of single U-tube wider, thermal resistance becomes lower. It is better to keep turbulent flow for making the amount of heat transfer by convection much.
収録刊行物
-
- 空気調和・衛生工学会大会 学術講演論文集
-
空気調和・衛生工学会大会 学術講演論文集 2004.3 (0), 1671-1674, 2004