D-49 少水量対応型地中熱ヒートポンプビルマルチシステムの開発 : その2 少水量時における地中熱交換器の採放熱性能検証試験

DOI

書誌事項

タイトル別名
  • D-49 Development of a Low Flow Circulation Ground Source Heat Pump Multi-split System : Part-2 Field experiment to investigate performance of the GHEX applying low flow circulation

抄録

Field experiment with foundation piles as ground heat exchangers (GHEX) applying low flow circulation (LF) has been carried out since October 2006 in order to develop the LF-GHEX. The LF-GHEX can extract or inject nearly equal heat to the conventional GHEX even in a case where the low flow circulation system is adopted in the primary side. As the result, the authors confirmed that several GHEXs with flow rate of 8L/min extracted nearly equal heat to the conventional one with flow rate of 16L/min. In addition, the variation of temperature calculated by a simulation program for the GHEX could reproduce the measured one.