G-10 浴室周りの換気空調システムの設計評価手法に関する研究 : その4 入浴後の浴室ドア開閉にともなう脱衣室内の湿気挙動に関するCFD解析

DOI

書誌事項

タイトル別名
  • G-10 Design and Evaluation of Ventilation System in Bathroom : Part 4 CFD Analysis of Humidity Distribution in Dressing Room after Bathing

抄録

CFD analysis on ventilation system for bathroom and dressing room where large amount of moisture was produced was carried out. Two type models, static plane model and dynamic plane model, were adopted with a door of the bathroom. By the comparison of the result of CFD analysis and experiment, the humidity diffusion between static plane model and dynamic plane model in the dressing room was greatly different, and it was found that it was important to take dynamic models into consideration for an analysis of humidity distribution in a dressing room.