F-13 サーマルマネキンによる各種暖房方式の快適性と投入熱量の評価

DOI

書誌事項

タイトル別名
  • F-13 Evaluation of Thermal Comfort and Heat Input for Heating Systems based on Thermal Manikin Measurement

抄録

In this experiment, the thermal comfort and heat input for heating systems (floor heating and air conditioner) based on thermal manikin measurement were compared. The experiment for the thermal manikin was performed in the artificial climate chamber. In that chamber, for floor heating and air conditioner the experimental condition was chosen as 18/20/22/24℃ for preset temperature, 5℃ for outside air temperature. In the result, the air temperature by floor heating was lower than that by air conditioner under the thermal neutrality. About heat input under the thermal neutrality, floor heating was 880W and air conditioner was 1354W.