高周波変圧器用ラップ接合アモルファス巻鉄心の鉄損算定

DOI

書誌事項

タイトル別名
  • Iron loss estimation of amorphous wound core with lap-joint for high-frequency transformers

抄録

<p>  To investigate loss-reduction schemes for the lap-joint amorphous wound core of the high-frequency transformer (HFT) of the isolated DC-DC converter used in the HVDC grid system, we tested the frequency, f performance of iron loss, Pi, of two types of amorphous HFTs up to 6 kHz. Their cores had the same specifications except for the mean magnetic path length. From the Pi-difference between them, the loss density in the laminated part of the amorphous foils, Wu, and the net loss induced by the crossing flux at the lap-joint part, PL, could be estimated separately. By parameter-fitting with the iron loss equation, it was revealed that Wu had an eddy-current loss coefficient that was close to that of the previously studied results for as-cast amorphous foils, and PL increased in proportion to square of f. We also discuss the impact of the lap-joint structure on the total loss of HFT in an electromagnetic analysis.</p>

収録刊行物

詳細情報 詳細情報について

  • CRID
    1390001205826218624
  • NII論文ID
    130006731077
  • DOI
    10.20819/msjtmsj.18tr205
  • ISSN
    24320471
  • 本文言語コード
    ja
  • データソース種別
    • JaLC
    • CiNii Articles
  • 抄録ライセンスフラグ
    使用不可

問題の指摘