押出成形アルミ均熱板で被覆された中空パイプ方式温水床暖房の放熱特性

書誌事項

タイトル別名
  • HEATING PERFORMANCE OF A HOT WATER FLOOR-HEATING SYSTEM WITH EXTRUDED ALUMINUM THERMO-UNIFORMITY PLATE AND HEAT PIPE
  • オシダシ セイケイ アルミキンネツバン デ ヒフク サレタ チュウクウ パイプ ホウシキ オンスイ ユカダンボウ ノ ホウネツ トクセイ

この論文をさがす

抄録

The purpose of this paper is to improve the performance of the HOT WATER FLOOR-HEATING SYSTEM WITH HEAT PIPE by solving the problems suggested in the previous paper. The problems were uneven temperature of the floor surface and slow temperature rising. THERMO-UNIFORMITY PLATE were developed to solve the problems. Effect of this member was verified in the artificial climate room. The results are as follows; Because of improvement of THERMO-UNIFORMITY PLATE from plywood covered with aluminum foil to Aluminum extrusion panel, 1) The heat transfer from pipe to THERMO-UNIFORMITY PLATE was promoted extremely. 2) Heating performance can be improved by about 30 %. 3) Accordingly uneven temperature and rising speed of temperature of floor surface were improved.

収録刊行物

詳細情報 詳細情報について

問題の指摘