Reform of the Correlation for the Prediction of Heat Transfer Coefficient for Refrigerants Flowing in Horizontal Evaporator Tubes

  • MORI Hideo
    Department of Mechanical Science and Engineering, Kyushu University
  • YOSHIDA Suguru
    Department of Mechanical Science and Engineering, Kyushu University
  • KAKIMOTO Yasushi
    Department of Energy and Mechanical Engineering, Graduate School, Kyushu University
  • OHISHI Katsumi
    Department of Mechanical Science and Engineering, Kyushu University

Bibliographic Information

Other Title
  • 冷媒の水平平滑蒸発管内熱伝達係数の予測式の修正
  • レイバイ ノ スイヘイ ヘイカツ ジョウハツカンナイ ネツ デンタツ ケイスウ ノ ヨソクシキ ノ シュウセイ

Search this article

Abstract

The authors had previously proposed a prediction method of the local heat transfer coefficient for pure refrigerants flowing in horizontal smooth evaporator tubes. This method was compared with new experimental data, and found not to be accurately applicable to refrigerants of a large vapor density and/or flow in a tube of small diameter, particularly in the separated flow regime1nthis prediction method, the separation angle is a primary factor, and correlation of this angle is used not only to classify the flow regime into the annular flow and the separated flow, but also to determine the ratio of the wet perimeter to the whole perimeter f the tube for the separated flow. Based on the new experimental data of the separation angle obtained for refrigerants of a large vapor density and in a small diameter tube, the correlation for the separation angle was reformed so that the predicted heat transfer coefficient agrees well also with the new experimental values.

Journal

Citations (4)*help

See more

References(46)*help

See more

Details 詳細情報について

Report a problem

Back to top