N<sub>2</sub>/SF<sub>6</sub>混合ガス絶縁電力機器の絶縁設計に関する基礎的考察

書誌事項

タイトル別名
  • Fundamental Study on Electrical Insulation Design of N<sub>2</sub>/SF<sub>6</sub> Gas Insulated Electric Power Apparatus
  • N2/SF6混合ガス絶縁電力機器の絶縁設計に関する基礎的考察
  • N2/SF6 コンゴウ ガス ゼツエン デンリョク キキ ノ ゼツエン セッケイ ニ カンスル キソテキ コウサツ

この論文をさがす

抄録

In this paper, we carried out a case study on fundamental insulation design for the application of N2/SF6 gas mixtures to 275kV gas-insulated busbar. Firstly, we investigated the impulse ratio in N2/SF6 gas mixtures and pointed out that the insulation design might be based on the negative switching impulse voltage in the case of lower SF6 content. Secondly, we estimated the tank diameter and SF6 gas amount with consideration of the electric field strength on conductor surface and temperature rise in gas mixtures. We clarified that the tank diameter at the lower SF6 content is mainly determined by the electric field strength on the conductor surface and quantified the optimum gas pressure and SF6 content for a target reduction of SF6 gas amount.

収録刊行物

被引用文献 (4)*注記

もっと見る

参考文献 (14)*注記

もっと見る

詳細情報 詳細情報について

問題の指摘

ページトップへ