- Analysis of the Phenomenon Associated with the Short Circuit of Shinkansen Changeover Switch and Development of New Type Protective Relay
- シンカンセン キリカエ カイヘイキ デンキョク カン タンラク コショウ ニ トモナウ カイロ ゲンショウ カイセキ ト コショウ ケンシュツ ケイデンキ ノ カイハツ
この論文をさがす
抄録
At substations or sectioning posts of Shinkansen, a pair of single-phase power sources are provided in different phase. When a Shinkansen car passes the boundary between the two power sources, the changeover section (about 1km long) with a pair of vacuum changeover switches the power sources for the car instantly.<br> There were no ways to detect the flashover of vacuum switch used as a changeover switch before, so we wasted a long time sometimes to specify the fault reason.<br> We analyzed the fault current carefully, to find the facts:<br> When the changeover switches are normal, a current flows through only one switch.<br> When the fault occurs on a changeover switch with no cars in the changeover section, fault current flows through both switches to make the currents in the two switches the same.<br> When a fault occurs on a changeover switch with a car in the changeover section, both fault current and load current flow. In this situation the currents in the two switches are different.<br> Then we have developed a new type protective relay for Shinkansen changeover switches based upon the facts. This relay has a pair of over current detectors with a pair of optical current transformers to detect the current in each changeover switch. When it detects the over current of both switches, it can judge that a flashover has occurred in one of the changeover switches.
収録刊行物
-
- 電気学会論文誌B(電力・エネルギー部門誌)
-
電気学会論文誌B(電力・エネルギー部門誌) 122 (4), 498-505, 2002
一般社団法人 電気学会
- Tweet
キーワード
詳細情報 詳細情報について
-
- CRID
- 1390282679581015296
-
- NII論文ID
- 10007983666
-
- NII書誌ID
- AN10136334
-
- ISSN
- 13488147
- 03854213
-
- NDL書誌ID
- 6123210
-
- データソース種別
-
- JaLC
- NDL
- Crossref
- CiNii Articles
-
- 抄録ライセンスフラグ
- 使用不可