水トリー劣化架橋ポリエチレンの残留電荷の測定と解釈  [in Japanese] Measurement and Interpretation of Residual Charge in Crosslinked Polyethylene Degraded by Water Trees  [in Japanese]

Access this Article

Search this Article

Author(s)

Abstract

The possibility whether measurement of residual charge is usable as a tool to detect water trees in crosslinked polyethylene is discussed. The results obtained are summarized as follows. (1) Residual charge was not measured in a sheet sample because of its small electrode area. (2) Residual charge was detected in a cable sample. (3) A clear frequency dependence of the residual charge was not observed. A model of the residual charge measurement is proposed, where the charges accumulated in a water tree are oscillated by ac electric field and are diffused through the water tree path with a high conductivity.

Journal

  • IEEJ Transactions on Fundamentals and Materials

    IEEJ Transactions on Fundamentals and Materials 122(6), 597-603, 2002-06-01

    The Institute of Electrical Engineers of Japan

References:  25