Surge Voltages Induced in Secondary Circuits of 275 kV Full GIS
-
- Hatano Ryosuke
- Chubu Electric Power Co., Inc.
-
- Ueda Toshiaki
- Chubu Electric Power Co., Inc.
-
- Nojima Kenichi
- TMT&D Corporation
-
- Motoyama Hideki
- Central Research Institute of Electric Power Insdustry
この論文をさがす
抄録
The study of surge voltage levels induced in low voltage control or monitoring circuits by lightning surges is very important for the rational design of those circuits in substations. To investigate the induction levels in those circuits, we carried out full-scale lightning impulse tests in a new 275kV full GIS substation. The obtained data clarified that the induced surge levels are under the testing levels of related standards. We analyzed the surge waveforms in the Potential Transformer (PT) secondary circuit by EMTP. The analysis indicated that induced surge levels are almost decided by the ratio of winding and the overvoltage level in a main circuit.
収録刊行物
-
- 電気学会論文誌B(電力・エネルギー部門誌)
-
電気学会論文誌B(電力・エネルギー部門誌) 123 (11), 1313-1318, 2003
一般社団法人 電気学会
- Tweet
詳細情報 詳細情報について
-
- CRID
- 1390001204601805696
-
- NII論文ID
- 10012556022
-
- NII書誌ID
- AN10136334
-
- ISSN
- 13488147
- 03854213
-
- NDL書誌ID
- 6751184
-
- 本文言語コード
- en
-
- データソース種別
-
- JaLC
- NDL
- Crossref
- CiNii Articles
-
- 抄録ライセンスフラグ
- 使用不可