Deterioration of Insulated Wire by Corona Discharge

  • Yamashita Takahiko
    Department of Electrical and Electronic Engineering, Nagasaki University
  • Ishihara Takeshi
    Department of Electrical Engineering and Computer Science, Graduate School of Science and Technology, Nagasaki University
  • Kawaguchi Masashi
    Department of Electrical Engineering and Computer Science, Graduate School of Science and Technology, Nagasaki University
  • Fujishima Tomoyuki
    Department of System Science, Graduate School of Science and Technology, Nagasaki University
  • Matsuo Hisao
    Department of Electrical and Electronic Engineering, Nagasaki University
  • Furuta Masakazu
    Kumamoto Branch, Kyushu Electric Power Co., Inc.

Bibliographic Information

Other Title
  • コロナ放電による絶縁電線の劣化
  • コロナ ホウデン ニ ヨル ゼツエン デンセン ノ レッカ

Search this article

Abstract

In relation to the accidents due to bird nests in contact with overhead distribution lines, the authors investigated on deterioration of covered conductor by corona discharge. To simulate the situation where conductive nest material such as wire is in contact with both of an arm and a covered conductor, a copper wire was wound around the covered conductor and was grounded through a resistor which is used to observe corona discharge current waveform. The state of normal operation of 6.6kV distribution line was considered and A.C. 3.8kV was applied between the conductor and the ground. Weak corona discharge was observed. In order to carry out the acceleration test, A.C. 6.6kV was applied. The insulation was punctured after 3760 hours. From the observation of cumulative charge by corona discharge the acceleration factor was estimated about 4. From the acceleration factor estimated, the life of conductor cover will be 627 days.

Journal

Citations (11)*help

See more

References(5)*help

See more

Details 詳細情報について

Report a problem