核融合における電力技術I 2. トカマク用電源技術 2.2 フライホイール電動発電機 [in Japanese] Power System for Tokamak Fusion Experiments Motor Generator with Flywheel Effect [in Japanese]
Access this Article
Search this Article
Author(s)
Abstract
JT-60 requires an enormous electric power pulse about 1,300 MVA periodically for its plasma initiation, containment and heating. JT-60 could not receive all electric power from a commercial line for plasma experiment except about 160 MVA because the 275 kV commercial line has some limitations. Therefore JT-60 needs huge electric power sources. The power supply system of JT-60 has 3 motor generators (MG). The total capacity of MG is 1,115 MVA that consists of a toroidal MG (TMG), poloidal MG (PMG) and Heating power supply MG (HMG), and each MG has a huge flywheel effect. For example, TMG has a 4.02 GJ energy yield that consists of 6 disk flywheel. The total weight of flywheel of TMG is 650 ton. This report describes the structure, operating system, and maintenance history of 3 types of MG.
Journal
-
- Journal of plasma and fusion research
-
Journal of plasma and fusion research 73(4), 427-433, 1997-04-25