冷却面を有する置換換気室内の温度・汚染物濃度分布 : 熱プルームを組み込んだブロックモデルの適用

書誌事項

タイトル別名
  • TEMPERATURE AND CONTAMINANT CONCENTRATION DISTRIBUTION OF DISPALACEMENT VENTILATED ROOMS WITH COOLED WALL : Application of "block model" integrated with thermal plumes to displacement ventilated room
  • レイキャクメン オ ユウスル チカン カンキ シツナイ ノ オンド オセンブツ ノウド ブンプ ネツ プルーム オ クミコンダ ブロック モデル ノ テキヨウ

この論文をさがす

抄録

Displacement ventilation is an efficient way to make a good air quality for human being. But the cold draft from a cooled wall may destroy the thermal stratification and the air quality in the occupied zone is contaminated. Temperature and contaminant concentration distributions, thermal plumes and downdraft velocities were measured in the full-size experimental room with their experimental parameters as the internal heat load and simulated outdoor air temperatures. The downdraft was generated at the window between the experimental room and the cooled next room. Calculations of the temperature and concentration distribution are also conducted by the block model proposed by Togari et al. The calculated results were practically in good agreement with the measured one.

収録刊行物

被引用文献 (1)*注記

もっと見る

参考文献 (22)*注記

もっと見る

詳細情報 詳細情報について

問題の指摘

ページトップへ