Temporal Development of Partial Discharge and Its Application to Breakdown Prediction in SF_6 Gas

抄録

We measured the temporal change of partial discharge (PD) characteristics leading to breakdown in SF_6, gas for ac voltage application. At the final stage close to the breakdown, positive PD pulses with relatively high magnitude began to take place in the phase region near the applied voltage peak. This event was interpreted in terms of the change of PD type in SF_6 gas from streamer to leader. Optical observation also revealed that PD type transition occurred. With the results considered, the mechanisms of PD were discussed. Moreover, we discussed the possibility of breakdown prediction in GIs. An attempt was made to find a breakdown prediction parameter which characterized the change of PD type: the ratio R_L of maximum charge to the average charge of PD pulses appearing in the phase region near the peak in positive half cycle. It was found that R_L, allowed to predict the time to breakdown successfully within the error of 4~20 %.