- 松崎 薫
- 東芝
書誌事項
- タイトル別名
-
- Technology for Highly Dependable Large Capacity UPS System.
- ダイキボ ム テイデン デンゲン システム ノ コウシンライカ ギジュツ
この論文をさがす
抄録
Our daily life is supported by powerful information networks which are composed of computers and communication equipments. If they do not work correctly or completely, our daily life would be surely confused. Under some circumstances safety could not be kept. Uninterruptible Power Supply (UPS) systems are commonly equipped to supply stable power to the critical loads, for example, large computer center telephone and telecomnication center, aviation control system and so on. Several kinds of UPS systems are now used in many important fields as the above mentioned. But they almost do not have been evaluated numerically based on system reliability.<br>This paper evaluates MTBF of parallel redundant UPS systems, and reports MTBF of 2 sets of parallel redundant UPS system is lower than that of 3 sets of parallel redundant UPS system under some circumstances. Continuous power supply reliability of the UPS system with bypass and uninterruptible transfer switch is much higher than any other UPS system without bypass circuit and uninterruptible transfer switch. And then the last some highly reliable parallel operation technology are shown.
収録刊行物
-
- 電気学会論文誌D(産業応用部門誌)
-
電気学会論文誌D(産業応用部門誌) 114 (3), 260-267, 1994
一般社団法人 電気学会
- Tweet
詳細情報 詳細情報について
-
- CRID
- 1390001204656225152
-
- NII論文ID
- 130000958232
-
- NII書誌ID
- AN10012320
-
- ISSN
- 13488163
- 09136339
-
- NDL書誌ID
- 3873411
-
- 本文言語コード
- ja
-
- データソース種別
-
- JaLC
- NDL
- Crossref
- CiNii Articles
-
- 抄録ライセンスフラグ
- 使用不可