Surface Tension Measurement for a New Low-GWP Refrigerant HFO-1123 by a Differential Capillary Rise Method

  • KONDOU Chieko
    Graduate School. Engineering, Division of System Science, Nagasaki University
  • HIGASHI Yukihiro
    NEXT-RP in WPI- International Institute for Carbon-Neutral Energy Research, Kyushu University

この論文をさがす

抄録

<p>By a differential capillary rise method, the surface tension was measured for a new candidate of low GWP refrigerant HFO-1123. 16 points of surface tension data with a propagated uncertainty of approximately ±0.22 mN m-1 are presented in this paper. Based on the measured data, a Van der Waals type empirical correlation was proposed for HFO-1123: = 61.02 (1-T/Tcrit)1.30 [mN m-1], where Tcrit is a critical temperature of 331.7 K measured by Higashi and Akasaka. This empirical correlation agrees with the measured surface tension data at temperatures from 267 K to 304 K.</p>