A STUDY ON TEMPERATURE PREDICTION OF FIRE PLUME EJECTED FROM AN OPENING UNDER SOFFIT WITH H-BEAM BENEATH TIP

  • KANG Seunggoo
    Graduate School of Global Fire Science and Technology, Tokyo Univ. of Science
  • OHMIYA Yoshifumi
    Dept. of Architecture, Faculty of Science and Technology, Tokyo Univ. of Science
  • KIMURA Kei
    Nippon Steel Corporation

Bibliographic Information

Other Title
  • 庇先端下にH形鋼梁を設置した庇面下の開口噴出熱気流の温度予測に関する研究

Search this article

Abstract

<p>This study is an experimental study on behavior of the fire plume ejected from an opening under soffit with H-beam beneath the tip. We used a large-scale experimental apparatus. Also, experimental conditions are the opening size, soffit size, handrail, and fire source. The temperature prediction under the soffit is proposed by using the Watanabe model (predictions of ceiling jet temperature by combining a two-layer zone model) and the Ohmiya model (predictions of the vicinity of vertical wall temperature) in combination. It was confirmed that the calculated value and the experimental result mostly match.</p>

Journal

References(10)*help

See more

Details 詳細情報について

Report a problem